Electrical Load Calculator

Minimum service size for a single dwelling per CEC Rule 8-200 — the greater of Option A and Option B, with an NEC mode, every constant cited and the math shown.

This tool estimates calculated load per CEC Rule 8-200 for guidance only. Final design must be verified by a licensed electrician and approved by the local authority having jurisdiction. Provincial amendments (e.g. BC, Ontario, Alberta) may differ.

This tool estimates calculated load per CEC Rule 8-200 for guidance only. Final design must be verified by a licensed electrician and approved by the local AHJ. Provincial amendments may differ.

Single dwelling

Minimum service size

100 A

Calculated load
24,000 W
Calculated current
100 A
Governing method
Option B (area)
Flat alternative minimum (area ≥ 80 m²)
24,000 W
  • This tool estimates calculated load per CEC Rule 8-200 for guidance only. Final design must be verified by a licensed electrician and approved by the local AHJ. Provincial amendments may differ.
  • Option B governs — the calculated load is the greater of Option A (16,630 W) and Option B (24,000 W).
  • Based on CEC 26th edition (CSA C22.1:24), Canada (CEC base).
How this is calculated
  1. Basic load — 8-200(1)(a)(i)

    5000 W (first 90 m²) + 1000 W × blocks of 90 m² above

    = 5000 + 1000 × ceil(max(0, 185.8 − 90) ÷ 90)

    7,000 W

  2. Space heating + A/C — 8-200(1)(a)(ii) / Section 62 / 8-106(3)

    heating: 100% of first 10000 W + 75% of remainder; A/C at 100%; interlock takes the larger

    = heat 0 W, A/C 2,880 W, interlocked = no

    2,880 W

  3. Electric range — 8-200(1)(a)(iii)

    6000 W; if rating > 12 kW add 40% of the excess

    = range = 12 kW

    6,000 W

  4. Tankless/pool/spa water heater + EVSE — 8-200(1)(a)(iv), (a)(v)

    tankless / pool / spa water heaters and EVSE at 100% (EVSE may use the EVEMS-limited demand)

    = tankless WH 0 W + EVSE 0 W

    0 W

  5. Additional loads > 1500 W — 8-200(1)(a)(vi)

    25% of each additional load (electric range installed); a storage-tank water heater is an additional load

    = additional loads {3,000} W

    750 W

  6. Option A total — 8-200(1)(a)

    basic + heating/AC + range + tankless WH + EVSE + additional loads

    = 7,000 + 2,880 + 6,000 + 0 + 0 + 750

    16,630 W

  7. Option B — 8-200(1)(b) flat alternative minimum

    24000 W if area ≥ 80 m², else 14400 W — nothing is added on top

    = area 185.8 m²

    24,000 W

  8. Greater of A/B → current → service size

    max(A, B) ÷ 240 V, then next standard size

    = 24,000 ÷ 240 = 100 A → standard sizes {60, 100, 125, 150, 200, 225, 400}

    100 A service

How to do a CEC load calculation for a single dwelling

CEC Rule 8-200(1) sizes a single-dwelling service as the greater of two options. Take a 200 m² home with a 12 kW range and a 2,880 W air conditioner. Option A (itemized) is a 5,000 W basic load for the first 90 m², plus 1,000 W for each additional 90 m² (here 2,000 W), plus 2,880 W for the A/C and 6,000 W for the range — 15,880 W. Option B is a flat alternative minimum of 24,000 W (because the area is 80 m² or more) — nothing is added on top of it. Option B is greater, so the calculated load is 24,000 W ÷ 240 V = exactly 100 A, a 100 A service.

8-200(1)(a) vs 8-200(1)(b): which option governs?

Option A itemizes every load — the area basic load, space heating and A/C (with Section 62 demand factors and the 8-106(3) interlock), the range, tankless / pool / spa water heaters and EV charging at 100%, and any additional load over 1,500 W at its demand factor: 25% each when an electric range is installed, otherwise 100% of the first 6,000 W combined plus 25% of the excess (a storage-tank water heater is an additional load). Option B is a flat alternative minimum — 24,000 W when the living area is 80 m² or more, or 14,400 W when it is under 80 m². Nothing is added to it. You must size the service to whichever option produces the larger calculated load — in practice Option B acts as a 100 A floor for average homes, and Option A governs once heavy loads (electric heat, EV charging) push the itemized total past it.

Determining living area (Rule 8-110)

Living area drives the basic load, so measure it the way the code does. Count the ground floor and all above-grade floors at 100%. Count a basement only where the finished ceiling height exceeds 1.8 m, and then at 75% of its area. Exclude unheated, unfinished or crawl spaces.

Standard service / panel sizes

The calculator rounds the calculated current up to the next standard size.
Service sizeTypical use
60 ASmall or older dwellings (legacy)
100 AMost single dwellings without electric heat
125 ADwellings with A/C, EV charging or modest electric heat
150 ALarger homes with several heavy loads
200 AAll-electric homes, electric heat plus EV charging
225 A / 400 ALarge all-electric homes or multiple heavy loads

Electric range load — CEC 8-200(1)(a)(iii)

6,000 W up to 12 kW, plus 40% of the amount above 12 kW.
Range nameplateCalculated load
≤ 12 kW6,000 W
14 kW6,800 W
16 kW7,600 W
18 kW8,400 W

How an EV charger changes your load

Electric-vehicle supply equipment is added at 100% of its rating — a 48 A charger is roughly 11,520 W, which alone is about 48 A of calculated current and can push a 100 A service over the line. An energy-management system (EVEMS, Rule 8-106(10)) can cap the demand it adds, often letting an existing service stay compliant. Enter the EVEMS-limited value when one is installed.

Common load-calculation mistakes

  • Adding loads on top of Option B. 8-200(1)(b) is a flat alternative minimum — compare the itemized Option A against the bare 24,000 W / 14,400 W figure; heating, water heating and EV charging belong only in Option A.
  • Counting a storage-tank water heater at 100%. With an electric range installed, additional loads over 1,500 W — including a storage water heater — take a 25% demand factor. Only tankless, pool and spa heaters count at 100%.
  • Adding interlocked heating and A/C together. Rule 8-106(3) lets you count only the larger when they cannot run at once.
  • Using a stale code edition or ignoring provincial amendments. The constants differ by edition and by province.
  • Treating the result as a final design. It is an estimate — a licensed electrician and the AHJ must verify before any work.

Frequently asked questions

How do I calculate the electrical load for a house?+

Per CEC Rule 8-200(1), size a single dwelling on the greater of two options. Option A itemizes a 5,000 W basic load (first 90 m²) plus 1,000 W per additional 90 m², space heating/AC (Section 62 demand, 8-106(3) interlock), the range, tankless/pool/spa water heaters and EV charging at 100%, and additional loads over 1,500 W at demand factors (25% each when an electric range is installed). Option B is a flat alternative minimum — 24,000 W (≥80 m²) or 14,400 W (<80 m²) with nothing added on top. Divide the larger total by 240 V and round up to the next standard service size.

What size electrical service do I need?+

Take the calculated load in watts, divide by 240 V to get amps, then round up to the next standard size: 60, 100, 125, 150, 200, 225 or 400 A. Most modern single dwellings land on 100 A or 125 A; all-electric homes with heating and EV charging often need 200 A.

How is an electric range counted in a load calculation?+

CEC 8-200(1)(a)(ii) counts a single range as 6,000 W, plus 40% of any amount by which its nameplate exceeds 12 kW. A 14 kW range is 6,000 + 0.40 × 2,000 = 6,800 W.

Does this replace a licensed electrician?+

No. This is an estimating aid only. The final service design must be calculated and verified by a licensed electrician and approved by the authority having jurisdiction. Provincial amendments may change the constants used.

Methodology & sources

The single-dwelling calculation implements CEC Rule 8-200(1): the greater of the itemized Option A (8-200(1)(a)) and the flat alternative minimum of Option B (8-200(1)(b)). Space-heating demand uses the Section 62 factors and the 8-106(3) interlock; the electric range, tankless water heaters, EV charging and additional loads follow the rule's demand factors, including the 25% factor on additional loads when a range is installed. Every constant — 5,000 W, 1,000 W, 6,000 W, the 12 kW threshold, the 40% factor, 24,000 W / 14,400 W and the standard service sizes — lives in a versioned dataset keyed to the code edition, so a code change is a data change, not a logic change.

The NEC mode implements the Article 220.82 optional dwelling calculation with its own cited constants. Both modes are estimating aids only. A licensed electrician must verify the final design, and the authority having jurisdiction must approve it; provincial and local amendments may differ.

Last reviewed June 28, 2026. Estimates are indicative — verify against current product specs and local requirements before ordering.

We're committed to keeping these tools accurate and improving them over time. If you'd like to contribute to their accuracy, or you run into any issues or errors, please email us at info@tradesppl.com.