Heat Loss & Load Calculator

Room-by-room heating and cooling load for HVAC and hydronic design — transmission, infiltration and slab-perimeter losses in BTU/h and kW, with the math shown and sources cited.

Professional-grade estimate, not a full ACCA Manual J. This uses the recognized transmission and infiltration heat-loss equations. For permit or warranty compliance, a full Manual J by a qualified professional is required.

Your space

Heating load

15,455 BTU/h

Heating load
4.53 kW
Transmission
9,731 BTU/h
Infiltration
5,724 BTU/h
  • Professional-grade estimate using the recognized transmission and infiltration heat-loss equations — this is NOT a full ACCA Manual J. For permit or warranty compliance, a full Manual J by a qualified professional is required.
How this is calculated
  1. Exterior walls (U×A×ΔT)

    U × area × ΔT

    = 0.063 × 640 × 53

    2,120 BTU/h

  2. Windows (U×A×ΔT)

    U × area × ΔT

    = 0.3 × 120 × 53

    1,908 BTU/h

  3. Doors (U×A×ΔT)

    U × area × ΔT

    = 0.2 × 40 × 53

    424 BTU/h

  4. Roof / ceiling (U×A×ΔT)

    U × area × ΔT

    = 0.02 × 1,200 × 53

    1,272 BTU/h

  5. Slab-on-grade edge (slab perimeter)

    F × perimeter × ΔT

    = 0.54 × 140 × 53

    4,007 BTU/h

  6. Infiltration (air-change form)

    volume × ACH × 0.018 × ΔT

    = 12,000 × 0.5 × 0.018 × 53

    5,724 BTU/h

  7. Total heating load

    Σ transmission + slab + infiltration

    = 5,724 + 4,007 + 5,724

    15,455 BTU/h = 4.53 kW

How is a heat loss calculation done?

The design temperature difference is ΔT = indoor − outdoor. For a 70 °F indoor and a −7 °F outdoor design that is a 77 °F ΔT. Each surface loses heat by Q = U × area × ΔT, where the U-factor is 1 ÷ R. A wall with U 0.07 over a net 138 ft² loses 0.07 × 138 × 77 ≈ 744 BTU/h. Air leakage adds volume × ACH × 0.018 × ΔT — a 2,816 ft³ room at 1.2 ACH adds ≈ 4,683 BTU/h. The whole-building load is the sum of every surface plus infiltration plus the slab edge.

Slab-on-grade floors use the perimeter method, not area: Q = F × exposed perimeter × ΔT. This is the correct (and more accurate) way to model edge losses — area-based slab estimates are wrong. Results are reported in BTU/h and in W/kW.

Typical assembly R-values and U-factors

U = 1 ÷ R. These are whole-assembly R-values, the same ones the calculator uses; whole-wall R is lower than the cavity batt.
AssemblyR-valueU-factor
2×4 wall, R-13 batt (≈R-11 effective)110.091
2×6 wall, R-20 batt (≈R-16 effective)160.063
Vented attic, R-50500.020
Double-pane low-E window3.30.30
Triple-pane low-E + argon window5.60.18
Insulated steel / fiberglass door, R-550.20

Two forms of the infiltration equation

They agree for the same air volume: CFM = volume × ACH ÷ 60, and 1.08 = 0.018 × 60.
FormEquationUse when
Air-changevolume × ACH × 0.018 × ΔTYou know the ACH
Airflow1.08 × CFM × ΔTYou know the ventilation CFM

Cooling load — tons from BTU/h

1 ton = 12,000 BTU/h.
Cooling load (BTU/h)Tons
12,0001.0
18,0001.5
24,0002.0
36,0003.0
60,0005.0

This is an estimate, not a Manual J

This calculator uses the recognized transmission and infiltration heat-loss equations to produce a professional-grade estimate. It is not a full ACCA Manual J load calculation. For permit submissions, equipment warranties or any compliance use, a full Manual J performed by a qualified professional is required.

The cooling figure is a sensible gain only: heat through the envelope, air leakage and occupants. Sun through glass, humidity (latent load) and appliance heat vary by hour and season and are not part of it. Treat it as a first check, not an equipment size. A full Manual J and Manual S are essential before selecting cooling equipment.

Common heat-loss estimating mistakes

  • •Estimating slab loss by area. Slab-on-grade loses heat at the edge — use F × perimeter × ΔT, not a U-value over the floor area.
  • •Forgetting to subtract windows and doors from the gross wall area. Otherwise the glazing is counted twice.
  • •Using cavity R-value instead of whole-assembly R. Framing, sheathing and thermal bridging lower the effective R.
  • •Oversizing equipment off a cooling estimate. Short-cycling hurts comfort and efficiency — confirm with a full Manual J / Manual S.

FAQ

Frequently asked questions

How do I calculate the heat loss of a room?

Find the design temperature difference (indoor − outdoor), then add the loss through each surface (Q = U × area × ΔT, where U = 1 ÷ R), the slab edge (F × perimeter × ΔT) and air infiltration (volume × ACH × 0.018 × ΔT). The total is the heating load in BTU/h.

How many BTUs do I need to heat a room?

It depends on the insulation, glazing, air leakage and your climate, not just floor area. This calculator sums the transmission, slab-perimeter and infiltration losses at your design temperatures to give the BTU/h (and kW) you need.

Is this calculator a Manual J?

No. It is a professional-grade estimate using the recognized transmission and infiltration heat-loss equations. For permit or warranty compliance a full ACCA Manual J by a qualified professional is required. The cooling figure covers the envelope, air leakage and occupants only, and needs a Manual J / Manual S before sizing equipment.

What is the difference between heat loss and cooling load?

Heat loss is winter heating demand — conduction and air leakage out of the building. The cooling load adds solar gain through glass and internal gains from people and equipment, and is far more sensitive to orientation, shading and humidity, so it is harder to estimate.

Methodology & sources

Heat loss is computed with the recognized transmission and infiltration equations: Q = U × area × ΔT per surface (U = 1 ÷ R), the perimeter F-factor method for slab-on-grade (Q = F × perimeter × ΔT), and air leakage as volume × ACH × 0.018 × ΔT (equivalently 1.08 × CFM × ΔT). Full precision is carried throughout; results are reported in BTU/h and W/kW, and cooling additionally in tons (1 ton = 12,000 BTU/h).

This is a professional-grade estimate, not a full ACCA Manual J. For permit or warranty compliance a full Manual J by a qualified professional is required, and any cooling figure must be confirmed with a Manual J / Manual S before selecting equipment.

Last reviewed November 10, 2026. Estimates are indicative. Verify against current product specs and local requirements before ordering.

We're committed to keeping these tools accurate and improving them over time. If you'd like to contribute to their accuracy, or you run into any issues or errors, please email us at info@tradesppl.com.

Email info@tradesppl.com
Needed cookiesKeep you signed in, remember your settings and protect the site.
Always on