Room-by-room heating and cooling load for HVAC and hydronic design — transmission, infiltration and slab-perimeter losses in BTU/h and kW, with the math shown and sources cited.
Professional-grade estimate, not a full ACCA Manual J. This uses the recognized transmission and infiltration heat-loss equations. For permit or warranty compliance, a full Manual J by a qualified professional is required.
Heating load
15,455 BTU/h
Exterior walls (U×A×ΔT)
U × area × ΔT
= 0.063 × 640 × 53
2,120 BTU/h
Windows (U×A×ΔT)
U × area × ΔT
= 0.3 × 120 × 53
1,908 BTU/h
Doors (U×A×ΔT)
U × area × ΔT
= 0.2 × 40 × 53
424 BTU/h
Roof / ceiling (U×A×ΔT)
U × area × ΔT
= 0.02 × 1,200 × 53
1,272 BTU/h
Slab-on-grade edge (slab perimeter)
F × perimeter × ΔT
= 0.54 × 140 × 53
4,007 BTU/h
Infiltration (air-change form)
volume × ACH × 0.018 × ΔT
= 12,000 × 0.5 × 0.018 × 53
5,724 BTU/h
Total heating load
Σ transmission + slab + infiltration
= 5,724 + 4,007 + 5,724
15,455 BTU/h = 4.53 kW
The design temperature difference is ΔT = indoor − outdoor. For a 70 °F indoor and a −7 °F outdoor design that is a 77 °F ΔT. Each surface loses heat by Q = U × area × ΔT, where the U-factor is 1 ÷ R. A wall with U 0.07 over a net 138 ft² loses 0.07 × 138 × 77 ≈ 744 BTU/h. Air leakage adds volume × ACH × 0.018 × ΔT — a 2,816 ft³ room at 1.2 ACH adds ≈ 4,683 BTU/h. The whole-building load is the sum of every surface plus infiltration plus the slab edge.
Slab-on-grade floors use the perimeter method, not area: Q = F × exposed perimeter × ΔT. This is the correct (and more accurate) way to model edge losses — area-based slab estimates are wrong. Results are reported in BTU/h and in W/kW.
| Assembly | R-value | U-factor |
|---|---|---|
| 2×4 wall, R-13 batt (≈R-11 effective) | 11 | 0.091 |
| 2×6 wall, R-20 batt (≈R-16 effective) | 16 | 0.063 |
| Vented attic, R-50 | 50 | 0.020 |
| Double-pane low-E window | 3.3 | 0.30 |
| Triple-pane low-E + argon window | 5.6 | 0.18 |
| Insulated steel / fiberglass door, R-5 | 5 | 0.20 |
| Form | Equation | Use when |
|---|---|---|
| Air-change | volume × ACH × 0.018 × ΔT | You know the ACH |
| Airflow | 1.08 × CFM × ΔT | You know the ventilation CFM |
| Cooling load (BTU/h) | Tons |
|---|---|
| 12,000 | 1.0 |
| 18,000 | 1.5 |
| 24,000 | 2.0 |
| 36,000 | 3.0 |
| 60,000 | 5.0 |
This calculator uses the recognized transmission and infiltration heat-loss equations to produce a professional-grade estimate. It is not a full ACCA Manual J load calculation. For permit submissions, equipment warranties or any compliance use, a full Manual J performed by a qualified professional is required.
The cooling figure is a sensible gain only: heat through the envelope, air leakage and occupants. Sun through glass, humidity (latent load) and appliance heat vary by hour and season and are not part of it. Treat it as a first check, not an equipment size. A full Manual J and Manual S are essential before selecting cooling equipment.
FAQ
Find the design temperature difference (indoor − outdoor), then add the loss through each surface (Q = U × area × ΔT, where U = 1 ÷ R), the slab edge (F × perimeter × ΔT) and air infiltration (volume × ACH × 0.018 × ΔT). The total is the heating load in BTU/h.
It depends on the insulation, glazing, air leakage and your climate, not just floor area. This calculator sums the transmission, slab-perimeter and infiltration losses at your design temperatures to give the BTU/h (and kW) you need.
No. It is a professional-grade estimate using the recognized transmission and infiltration heat-loss equations. For permit or warranty compliance a full ACCA Manual J by a qualified professional is required. The cooling figure covers the envelope, air leakage and occupants only, and needs a Manual J / Manual S before sizing equipment.
Heat loss is winter heating demand — conduction and air leakage out of the building. The cooling load adds solar gain through glass and internal gains from people and equipment, and is far more sensitive to orientation, shading and humidity, so it is harder to estimate.
Calculate the room heating load, then size the radiant floor: required output, floor flux, PEX tubing length and loop count, flow in GPM and the boiler output and fuel input — with every formula shown.
OpenWork out the sensible cooling gain from heat through the envelope, air leakage and occupants, and convert it to tons. Sun through glass, humidity and appliance heat are not included, so this is a first check and not an equipment size.
OpenHeat loss is computed with the recognized transmission and infiltration equations: Q = U × area × ΔT per surface (U = 1 ÷ R), the perimeter F-factor method for slab-on-grade (Q = F × perimeter × ΔT), and air leakage as volume × ACH × 0.018 × ΔT (equivalently 1.08 × CFM × ΔT). Full precision is carried throughout; results are reported in BTU/h and W/kW, and cooling additionally in tons (1 ton = 12,000 BTU/h).
This is a professional-grade estimate, not a full ACCA Manual J. For permit or warranty compliance a full Manual J by a qualified professional is required, and any cooling figure must be confirmed with a Manual J / Manual S before selecting equipment.
Last reviewed November 10, 2026. Estimates are indicative. Verify against current product specs and local requirements before ordering.
We're committed to keeping these tools accurate and improving them over time. If you'd like to contribute to their accuracy, or you run into any issues or errors, please email us at info@tradesppl.com.